Controller for Large IDC Cooling and Industrial AC
Air Conditioning System Applicable
● Precision AC
● In-row AC
● High Heat Intensity AC
● Constant Temperature & Humidity AC
● Chiller
● Lab AC
Key features as follow
● Reliable error-proof protection: High/low pressure, Air flow loss…
● Multiple communication protocol: RS485, CAN, MODBUS RTU
● Teamwork Management: Rotate, Backup, synergy
● Easy Maintenance: Current Status and Alarms, 200 history alarms
● DIN installation
Type | UCO-L01 | UCO-L02 | ||
General Features | Input Voltage | 24VAC±15%, Max. Power: 40VA/15W | 24VAC±15%, Max. Power: 30VA/10W | |
Frequency | 50/60Hz | |||
Storage | -40℃~70℃, 90%RH, No condensation | |||
Operation | -30℃~60℃, 90%RH, No condensation | |||
IP | IP20 | |||
Interface | DI | 16 (Isolated optocoupler) | 6 (Isolated optocoupler) | |
DO | 12 (250VAC/5A Relay) 2 (SCR, Optional) | 5 (250VAC/5A Relay) | ||
AI | 4 (0~5VDC) | 2 (0~5VDC) | ||
AO | 3 (0~10VDC) | |||
Temperature and Humidity Measurement | 1 for Temperature, and 1 for Humidity | |||
NTC | 4 NTC | 1 NTC | ||
RS485 | 2, Max. trans-mission distance 1km | |||
CAN | 1 | |||
Mechanical Features | Dimension (L*W*H) | 312mm×120mm×50 mm | 140mm×120mm×50mm | |
Installation | DIN | |||
Safety / EMC | GB 4706、IEC61335 / IEC61000,EN55014(CISPR14) |